FEATURES ::
- Programmer, indicator and controller for transmitters with HART protocol
- Highly informative Dot-Matrix display back light
- Tank visualisation
- Menu-based 6-key programming
- 1 to 15 input channels
- Transmitter diagnostic capabilities
- Explosion-proof models
|
APPLICATIONS ::
- Programmer, indicator and controller for single transmitters and for transmitter groups
- RS485 comm. line with HART or MODBUS protocol
|
SPECIFICATIONS ::
- Power supply: 11.4-40 V DC, 11.4-28 V AC or 85-255 V AC
- Temperature: -30…+50 °C
- Input from transmitters: HART
- Outputs, (depending on order):
max. 2: 4-20 mA
max. 4: SPDT relays
RS 485
- Outputs, extended with PJK-100 universal interface modules:
max. 16: 4-20 mA
max. 64: SPDT relays
- Communication with host: RS 485
- Protection: IP65
- Approval: ATEX II (1) G (EEx ia) IIB
|
|
UNICONT PMM
|
|
|
FEATURES ::
- Dual channel
- Up to 4 relays
- Transmitter power supply
- 32 point linearisation
- Various control algorithms, Auto tuning
APPLICATIONS ::
-
SPECIFICATIONS ::
-
|
|
UNICONT PDF
|
|
|
FEATURES ::
- General field indication of process current
- Two-wire operation
- 4-20 mA input
- 3.5 digit LCD display
- 20 mm digit height
- Heavy duty field mountable housing
- Scaleable display
- EEX ia II c T5/T6
APPLICATIONS ::
-
SPECIFICATIONS ::
-
|
|
UNICONT PKK
|
|
|
FEATURES ::
- Loop monitoring capability and error indication by the current input
- Programmable mode of operation: limit/differential/window switch
- EEx ia version available
- Programmable input current
- Programmable switching delay
- Power relay output (SPDT, 8A rated)
|
APPLICATIONS ::
- Power supply unit and switching amplifier for any 2-wire transmitter
- Power supply unit for any 4-wire transmitter
- Switching amplifier in connection with a 4-wire active transmitter
|
SPECIFICATIONS ::
- Power supply: 24V, 110V, 230V AC, 24V AC/DC
- Input: 1...22mA
- Output: change over, 250V AC, 8A