Multi - Channel PDF Print E-mail

 

2100-A16 (Analogue Input Remote Station)


Stand Alone logging option

 2100-a16-pict
 

Memory Expansion Features:

  • Comms; RS232 or RS422.
  • Selectable sample rate;
    2, 5, 30 sec, 1, 2, 5, 10, 15, 30 min, 1 hour.
  • Samples stored in permanent memory.
  • Rolling buffer (first in first out).
  • Upload to Intech scada software via;
    • standard comms,
    • radio or telephone modem.
  • Memory; 32,000 samples.
  • Each sample contains 26 readings, consisting of;
    • 16 analogue input values
    • 2 analogue output values
    • 4 digital input state
    • 2 digital output state
    • 1 ambient temperature
    • 1 time and date of sample
 

Ordering Information:

Supplied included with the 2100-A16 (ready to operate):

 2100-a16me-ordering
 

Supplied seperately (for retro-fitting to the 2100-A16 - see installation guide above for instructions):

2100-ME-32

 

Notes:

  1. Only fit 2100-ME-32 to 2100-A16 Rev.1 RTU-32 or 2100-A16 Rev1.2
  2. The clock of the 2100-ME is operated by a supercap. The clock will be retained for typically 2 weeks with no power. When the power is re-applied the supercap recharges itself.
  3. Sample transfer rate of the flash memory is more than 300 samples/minute at 9600baud. The 2100-ME-32 takes approx. 104 minutes to upload.
  4. When samples are taken, only the spot values at that time are stored.
  5. The 2100-ME can be used when the PLC retransmission modes and Scada COMMS are operating. However, either the Scada must be stopped to read the samples out of the memory, or a seperate port must be used.
  6. The 2100-R cannot be used when the 2100-ME is installed.
  7. 2100-M values are not stored. The 2100-M driver does not operate with the 2100-ME installed.
  8. The 2100-ME cannot be used with RS485 Comms.
  9. 2100-ME Memory Board CANNOT be used when Modbus RTU protocol is used.